EasyManua.ls Logo

turck BL67 - Page 129

turck BL67
507 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D300529 0115 - BL67 I/O modules
6-41
BL67-2AI-TC, thermo couples
12-bit-representation (left-justified)
For the parameterization
"Type K, -270 … 1370 °C"
"Type B, +100 … 1820 °C"
"Type E, -270 … 1000 °C"
"Type J, -210 … 1200 °C"
"Type N, -270 … 1300 °C"
"Type R, -50 … 1760 °C"
"Type S, -50 … 1540 °C"
"Type T, -270 … 400 °C"
The value range:
-270 °C to 1820 °C
is displayed as follows:
EF2(0)
hex
bis 71C(0)
hex
(decimal: -270 to 1820)
The value range:
-50 mV to -0,024 mV;
-100 mV to -0,049 mV;
-500 mV to -0,244 mV;
-1000 mV to -0,489 mV;
is displayed as follows:
800(0)
hex
to FFF(0)
hex
(decimal: -2048 to -1)
The value range:
0 mV to 50 mV;
0 mV to 100 mV;
0 mV to 500 mV;
0 mV to 1000 mV;
is displayed as follows:
000(0)
hex
bis 7FF(0)
hex
(decimal: 0 to 2047)
NOTE
A detailed description of the measurement value representation for the analog input mod-
ules in 16 or 12 bit can be found in the Appendix of this manual, page 15-8.