D300529 0115 - BL67 I/O modules
6-37
BL67-2AI-TC, thermo couples
Diagnostic data
This module has the following diagnostic data per channel:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Diagnostics Meaning
6.5.4 Module parameters
-----Cold junction
compensation
wire break
Wire break Measured value
out of range
Table 6-25:
Diagnostics
Measured value out of range Threshold: 1 % of positive
measurement range end value
Wire break
Threshold: negative transformer end value
In temperature measurement ranges only
Cold junction compensation wire break If no Pt1000 sensor is detected, a cold junction
temperature of 23 °C is automatically presumed.
NOTE
Due to a product actualization, the
parameter texts of the TURCK-I/O-product have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 15-30)).
Standard
PROFIBU
S
PROFINET
Parameter
byte-
oriented
word-
oriented
Channel 0
Byte 0
Bit 0
Word 0
Bit 0
Byte 0
Bit 0 Mains suppression
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 Deactivate diagnostics
Bit 3 Bit 3 Bit 3 Deactivate channel
Bit 4 Bit 4 Bit 4 Thermocouple type
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Channel 1
Byte 1
Bit 0 Bit 8
Byte 1
Bit 0 Mains suppression
Bit 1 Bit 9 Bit 1 Data format
Bit 2 Bit 10 Bit 2 Deactivate diagnostics
Bit 3 Bit 11 Bit 3 Deactivate channel
Bit 4 Bit 12 Bit 4 Thermocouple type
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7