EasyManua.ls Logo

turck BL67 - Module Parameters

turck BL67
507 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog output modules
D300529 0115 - BL67 I/O modules8-24
8.4.4 Module parameters
NOTE
Due to a product actualization, the parameter texts of the TURCK-I/O-product have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 15-30)).
Standard
PROFIBUS
PROFINET
Parameter
byte-
oriented
word-
oriented
Channel 0
Byte 0
Bit 0
Word 0
Bit 0
Byte 0
Bit 0 Operation mode
Bit 1 Bit 1 Bit 1
Bit 2 Bit 2 Bit 2
Bit 3 Bit 3 Bit 3
Bit 4 Bit 4 Bit 4 Data format
Bit 5 Bit 5 Bit 5 Deactivate diagnostics
Bit 6 Bit 6 Bit 6 Output on module bus error
Bit 7 Bit 7 Bit 7
Byte 1
Bit 0 Bit 8
Byte 2
Bit 0 Substitute value (low byte)
Bit 1 Bit 9 Bit 1
Bit 2 Bit 10 Bit 2
Bit 3 Bit 11 Bit 3
Bit 4 Bit 12 Bit 4
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7
Byte 2
Bit 0
Word 1
Bit 0
Byte 1
Bit 0 Substitute value (high byte)
Bit 1 Bit 1 Bit 1
Bit 2 Bit 2 Bit 2
Bit 3 Bit 3 Bit 3
Bit 4 Bit 4 Bit 4
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7
Channel 1
Byte 3
Bit 0 Bit 8
Byte 3
Bit 0 Operation mode
Bit 1 Bit 9 Bit 1
Bit 2 Bit 10 Bit 2
Bit 3 Bit 11 Bit 3
Bit 4 Bit 12 Bit 4 Data format
Bit 5 Bit 13 Bit 5 Deactivate diagnostics
Bit 6 Bit 14 Bit 6 Output on module bus error
Bit 7 Bit 15 Bit 7

Table of Contents

Other manuals for turck BL67

Related product manuals