00529 0115 - BL67 I/O modules10-44
10.2.5 Measurement value representation
the measurement value representation corresponds to that of the module BL67-4AI4AO-VI.
Measurement value representation of the inputs, page 10-11
Measurement value representa
tion of the outputs, page 10-27
Table 11:
Module parame-
ters
A default
settings
B for in- and out-
puts
C only for
inputs
Operation mode 0000 = voltage, -10 … 10 VDC standard A, B
0001 = voltage, 0 … 10 VDC standard B
0010 = voltage, -10 … 10 VDC PA (NE 43) B
0011 = voltage, 0 … 10 VDC PA (NE 43) B
0100 = voltage, -10 … 10 VDC ext. range B
0101 = voltage, 0 … 10 VDC ext. range B
0110 = reserved
0111 = reserved
1000 = 0 … 20 mA standard A, C
1001 = 4 … 20 mA standard, C
1010 = 0 … 20 mA PA (NE 43) C
1011 = 4 … 20 mA PA (NE 43) C
1100 = 0 … 20 mA ext. range C
1101 = 4 … 20 mA ext. range C
1111 = deactivate
Data format 0 = 15 bit + sign
A
1 = 12 bit (left-justified)
Deactivate diagnostics 0 = no
A
1 = yes
Output on module bus error 0 = substitute value
A
1 = current value
Substitute value Ax Substitute value = "0"
A
1. The substitute value defined here will be sent in consequence of
certain events parameterized in the gateway.
or
2. In case of a module bus error: The substitute value defined here
will be sent if the parameter "Behavior module bus error Ax" is set
to "output substitute value".