D300529 0115 - BL67 I/O modules
12-25
BL67-1RS485/422
12.2.5 Diagnostic and status messages
LED status messages
Diagnostics
This module has the following diagnostic data per channel:
Diagnostic byte assignment, Process input data (page 12-18)
Diagnostic message
Table 12-4:
LED status mes-
sages
LED Display Meaning Remedy
D Red Module bus communication failure Check if more than two ad-joining
el
ectronics modules have been
pulled. This concerns modules
located between this module and
the gateway.
off No error messages or diagnostics
TxD Green Data transmission active
off No data transmission
RxD Green Data are currently received
off No data are received
Table 12-5:
Diagnostics
buffer overflow Buff Ovfl:
Overflow of the receive-buffer (RX-buffer).
Frame error Frame Err:
The module has to be parameterized for adaptation to the data
structure of the data terminal equipment (DTE).
A frame error occurs in case of inconsequent parameterization
(number of data bits, stop bits, method of parity, …).
Data flow control error
Data flow control
HndSh Err:
The DTE connected t the module does not react to XOFF or RTS
handshake.
The internal receive-buffer may overflow (buffer-overflow = 1).
Hardware error HW Faliure:
The module has to be replaced (e.g. error in EEPROM or UART)
Parameterization error Prm Err:
The parameter settings can not be supported.