Analog output modules
D300529 0115 - BL67 I/O modules8-6
8.2.4 Module parameters
NOTE
Due to a product actualization, the parameter texts of the TURCK-I/O-product have been
revised.
The actual configuration files (GSD-, GSDML-, EDS-files) with the new parameters can be
found under www.turck.com.
If you use older configuration files with old parameter texts (issue date before April 2014),
then you can find a cross reference list in the manual's appendix (see Cross reference list
parameters (page 15-30)).
Standard
PROFIBUS
PROFINET
Parameter
byte-
oriented
word-
oriented
Channel 0
Byte 0
Bit 0
Word 0
Bit 0
Byte 0
Bit 0 Output range
Bit 1 Bit 1 Bit 1 Data format
Bit 2 Bit 2 Bit 2 reserved
Bit 3 Bit 3 Bit 3 Deactivate channel
Bit 4 Bit 4 Bit 4 Output on module bus error
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6 Data representation
Bit 7 Bit 7 Bit 7
Byte 1
Bit 0 Bit 8
Byte 2
Bit 0 Substitute value (low byte)
Bit 1 Bit 9 Bit 1
Bit 2 Bit 10 Bit 2
Bit 3 Bit 11 Bit 3
Bit 4 Bit 12 Bit 4
Bit 5 Bit 13 Bit 5
Bit 6 Bit 14 Bit 6
Bit 7 Bit 15 Bit 7
Byte 2
Bit 0
Word 1
Bit 0
Byte 1
Bit 0 Substitute value (high byte)
Bit 1 Bit 1 Bit 1
Bit 2 Bit 2 Bit 2
Bit 3 Bit 3 Bit 3
Bit 4 Bit 4 Bit 4
Bit 5 Bit 5 Bit 5
Bit 6 Bit 6 Bit 6
Bit 7 Bit 7 Bit 7