D300529 0115 - BL67 I/O modules
6-69
BL67-4AI-TC, thermo element
Basic errors and repeat accuracies
A For temperatures outside the defined measurement range, higher deviations for basic error
and repeat accuracy are possible.
Table 6-36:
Basic error -
nominal ranges A
Thermo couple Nominal range for
Basic error at 23 °C/73.4 °F
0,2 % from end value
Repeat accuracy/%
% of positive end value
Type B 750 … 1820 °C 0.05
Type C 0 … 2315 °C (15 bit + sign)
0 … 2047 °C (12 bit)
0.05
Type G 0 … 2315 °C (15 bit + sign)
0 … 2047 °C (12 bit)
0.05
Type E -200 … 1000 °C 0.05
Type J -210 … 1200 °C 0.05
Type K -200 … 1370 °C 0.05
Type N -200 … 1300 °C 0.05
Type R 75 … 1760 °C 0.05
Type S 75 … 1760 °C 0.05
Type T -200 … 400 °C 0.05
Voltage measurement all measurement ranges 0.05