Digital combi modules
D300529 0115 - BL67 I/O modules9-22
Diagnostic data
This module has the following diagnostic data available
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
:
Diagnostics
0 ----Overcurrent
sensor supply
D
Over
current
sensor supply
C
Overcurrent
sensor supply
B
Overcurrent
sensor supply
A
1 ----Output signal
overcurrent
Ch3
Output signal
overcurrent
Ch2
Output signal
overcurrent
Ch1
Output signal
overcurrent
Ch0
Table 9-15:
Diagnostics
Overcurrent sensor supply Short-circuit or overload at
sensor supply A, B, C or D (see Table 9-11:)
Output signal overcurrent Short-circuit or overload at output x
The channel is switched off automatically.
For the for switching-off characteristics of the
outputs see Technical data Table 9-2:.