NOTE
General technical Data of BL67 modules
D3
00529 0115 - BL67 I/O modules3-8
Static electricity accor
ding to IEC 61131 -2
Electromagnetic HF fields according to IEC 61131 -2
Fast transients (Burst) according to IEC 61131 -2
Conducted interferences
induced by HF fields
according to IEC 61000-4-6
10 V
Criteria A
A I/O-line-length ≤
30 m
High energy transients (Surge) A
Voltage range
according to IEC 61000-4-5
0,5 kV CM, 12Ω/ 9 μF
0,5 kV DM, 2Ω/ 18 μF
Criteria B
Reliability
min. 120 000 h
Pull/plug cycles of electronic modules 20
This device can cause radio disturbances in residential areas and in small industrial areas (res-
idential, business and trading). In this case, the operator can be required to take appropriate
measures to suppress the disturbance at his own cost.