D300529 0115 - BL67 I/O modules
10-19
BL67-4AI4AO-VI, voltage/current
0 … 10 V bipolar Diagnostics dec. hex.
voltage value U
M
= (dec. value/16 × 5,787 × 10
-3
) V
≥ 11.8460 V
overflow
2047 × 16 7FF0
≥ 11.7592 V
at ↑ DIA Measured value out
of range
ON
2032 × 16 7F00
11.7535 V
over-
drive
2031 × 16 7EF0
≤ 11.6030 V
at ↓ DIA Measured value out
of range
OFF
2005 × 16 7D50
10.0058 V 1729 × 16 6C10
10.000000 V
nominal range
1728 × 16 6C00
………
5.0000 V 864 × 16 3600
………
0.000578 V 1 × 16 0010
0.00000 V 0 0000
≥ -0.050 V
underflow
at ↑ DIA Overflow/underflow
OFF
00000
< -0,100 V
at ↓ DIA Overflow/underflow
ON
00000
0 … 20 mA bipolar Diagnostics dec. hex.
current value
M
= (dec. value/16 × 0,01157) mA
≥ 23.6921 mA
overflow
2047 × 16 7FF0
≥ 23.51852 mA
at ↑ DIA Measured value out
of range
ON
2032 × 16 7F00
23.5069 mA
over-
drive
2031 × 16 7EF0
≤ 23.2060 mA
at ↓ DIA Measured value out
of range
OFF
2005 × 16 7D50
20.0116 mA 1729 × 16 6C10
20.000000 mA
nominal range
1728 × 16 6C00
………
10.0000 mA 864 × 16 3600
………
0.01157 mA 1 × 16 0010
≤ 0.0000 mA 0 0000
≥ -0,1 mA
underflow
at ↑ DIA Overflow/underflow
OFF
00000
< -0,2 mA
at ↓ DIA Overflow/underflow
ON
0 … 0000