D300529 0115 - BL67 I/O modules
10-23
BL67-4AI4AO-VI, voltage/current
4 … 20 mA unipolar Diagnostics dec. hex.
current value
M
= (dec. value × 0,001) mA
≥ 22,000 mA
overflow
at ↑ DIA Overflow/under-
flow
ON
22000 55F0
≤ 21.999 mA
at ↓ DIA Overflow/underflow
OFF
21999 55EF
21.001 mA
at ↑ DIA Measured value out
of range
ON
21001 5209
≥ 21.000 mA
over-
drive
21000 5208
≤ 20.500 mA
at ↓ DIA Measured value out
of range
OFF
20500 5014
20.001 mA 20001 4E21
20,000 mA
nominal range
20000 4E20
………
12.000 mA 12000 2EE0
………
4.001 mA 4001 0FA1
4.000 mA 4000 0FA0
3.999 mA
under-
drive
3999 0F9F
≥ 3.800 mA
at ↑ DIA Measured value out
of range
OFF
3800 0ED8
3.600 mA
at ↓ DIA Measured value out
of range
ON
3600 0E10
3.599 mA
underflow
3599 0E0F
≥ 2,001 mA
at ↑ DIA Wire break OFF 2001 07D1
≤ 2.000 mA
at ↓ DIA Wire break ON 2000 07D0
0.000 mA 0000 0000