Appendix
D300529 0115 - BL67 I/O modules15-12
The value range:
0 °C to 850 °C
is displayed as follows:
0000
hex
to 2134
hex
(decimal: 0 to 8500)
For the parameterization
"Pt100, -200 … 150 °C"
"Ni100, -60 … 150 °C"
"Pt200, -200 … 150 °C"
"Pt500, -200 … 150 °C"
"Pt1000, -200 … 150 °C"
"Ni1000, -60 … 150 °C"
use the equation:
temperature value = 0,1°C × decimal value
The value range:
-200 °C to -0,01°C
is displayed as follows:
B1E0
hex
to FFFF
hex
(decimal: -20000 to -1)
The value range:
0 °C to 150 °C
is displayed as follows:
0000
hex
to 3A98
hex
(decimal: 0 to 15000)
For representation of resistance values only positive numbers (hexadecimal/binary) are used. The pos-
itive values can easily be converted into decimal ones.
The value range:
0 to 100 Ω; 0 to 200 Ω; 0 to 200 Ω; 0 to 1000 Ω
is displayed as follows:
0000
hex
to 7FFF
hex
(decimal: 0 to 32767)
The resistance values can now be calculated according to the parameterization.
The following equations are valid:
"Resistance, 0 … 100 Ohm":
Resistance value = 0,00305
Ω
× decimal value
"Resistance, 0 … 200 Ohm":
Resistance value = 0,00613
Ω
× decimal value