D300529 0115 - BL67 I/O modules
15-33
Cross reference list parameters
Channel Deactivate channel
0 = activate
1 = deactivate
0 = no
1 = yes
Mains suppression
0 = 50 Hz
1 = 60 Hz
Voltage mode (AI) Measurement range
0 = 0 … 10 V
1 = -10 … +10
Voltage mode (AO) Output range
0 = 0 … 10 V
1 = -10 … +10 V
Current mode (AI) Measurement range
0 = 0 … 20 mA
1 = 4 … 20 mA
Current mode (AI) Output range
0 = 0 … 20 mA
1 = 4 … 20 mA
Value representation Data format
0 = Integer (15 bit + sign)
1 = 12 bit (left justified)
0 = 15 bit + sign
1 = 12 bit (left-justified)
Value representation Data representation
00 = standard
01 = NE43
10 = extended range
Technology modules
BL67-1RS232/BL67-1RS485/422
Transmission rate
0000 = 300 bps
0001 = 600 bps
0010 = 1200 bps
0100 = 2400 bps
0101 = 4800 bps
0110 = 9600 bps
0111 = 14400 bps
1000 = 19200 bps
1001 = 28800 bps
1010 = 38400 bps
1011 = 57600 bps
1100 = 115200 bps
Data bits
0 = 7
1 = 8
Table 15-5:
Cross reference list
parameters