Table 75: Setpoint settings
Index Parameter Min Max Unit Default ID Description
P3.13.2.1 Keypad Setpoint 1
P3.13.1.
5
P3.13.1.
6
P3.13.1
.4
0 167
P3.13.2.2 Keypad Setpoint 2
P3.13.1.
5
P3.13.1.
6
P3.13.1
.4
0 168
P3.13.2.3 Setpoint Ramp Time 0.00 300.0 s 0.00 1068
P3.13.2.4
PID Setpoint Boost
Activation
Varies Varies
DigIN
Slot0.1
1046
OPEN = No boost
CLOSED = Boost
P3.13.2.5
PID Setpoint Selec-
tion
Varies Varies
DigIN
Slot0.1 *
1047
OPEN = Setpoint 1
CLOSED = Setpoint 2
P3.13.2.6
Setpoint Source 1
Selection
0 33 3 * 332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input
1
18 = Temperature input
2
19 = Temperature input
3
20 = Temperature input
4
21 = Temperature input
5
22 = Temperature input
6
23 = Block Out.1
24 = Block Out.2
25 = Block Out.3
26 = Block Out.4
27 = Block Out.5
28 = Block Out.6
29 = Block Out.7
30 = Block Out.8
31 = Block Out.9
32 = Block Out.10
33 = Multi-setpoint
VACON · 164 PARAMETERS MENU