Vaisala WXT530 Series - Parameter Order for SDI-12 Mode

Vaisala WXT530 Series
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
An example of MDA:
$WIMDA,29.88,I,1.0120,B,22.5,C,,C,31.5,,,C,,T,,M,,N,,M*3F
Examples (
ASCII and NMEA 0183, device address 0)
You need the temperature and humidity data to be available in every 30 seconds
Changing the parameter selection:
0TU,R=0101000001010000<cr><lf>
0TU,R=01010000&01010000<cr><lf>
Character '&' is not allowed in the command.
Changing the update interval:
0TU,I=30<cr><lf>
0TU,I=30<cr><lf>
The r
esponse after the change:
0R2<cr><lf>
0R2,Ta=23.9C,Ua=26.7P<cr><lf>
Example (
SDI-12, device address 0)
Changing the temperature unit to Fahrenheit:
0XTU,U=F!0<cr><lf>
To check the da
ta content in SDI-12 mode, you must type 0XTU!.
WXT530 Series User Guide M211840EN-D
126