B.3 Parameter Table
386 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n F3: Digital Input Card (DI-A3)
n F4: Analog Monitor Card (AO-A3)
No.(Addr.) Name Description Setting Page
F3-01
(390H)
Digital Input Option Card Input
Selection
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
The value set to F3-03 determines the setting range and units as follows:
F3-03 = 0: 100%/255 (-255 to +255)
F3-03 = 1: 100%/4095 (-4095 to +4095)
F3-03 = 2: 100%/30000 (-33000 to +33000)
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2 or 3),
the units for F3-01 are determined by parameter o1-03.
Default: 0
Min: 0
Max: 7
176
F3-03
(3B9H)
Digital Input Option DI-A3 Data
Length Selection
0: 8 bit
1: 12 bit
2: 16 bit
Default: 2
Min: 0
Max: 2
177
No.(Addr.) Name Description Setting Page
F4-01
(391H)
Terminal V1 Monitor Selection
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits of
the desired U- monitor. Some U parameters are available only in certain control modes.
Default: 102
Min: 000
Max: 999
177
F4-02
(392H)
Terminal V1 Monitor Gain
Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
177
F4-03
(393H)
Terminal V2 Monitor Selection
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of
the desired U- monitor. Some U parameters are available only in certain control modes.
Default: 103
Min: 000
Max: 999
177
F4-04
(394H)
Terminal V2 Monitor Gain
Sets the gain for voltage output via terminal V2.
Default: 50.0%
Min: -999.9%
Max: 999.9%
177
F4-05
(395H)
Terminal V1 Monitor Bias
Sets the amount of bias added to the voltage output via terminal V1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
177
F4-06
(396H)
Terminal V2 Monitor Bias
Sets the amount of bias added to the voltage output via terminal V2.
Default: 0.0%
Min: -999.9%
Max: 999.9%
177
F4-07
(397H)
Terminal V1 Signal Level
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
178
F4-08
(398H)
Terminal V2 Signal Level
Default: 0
Min: 0
Max: 1
178