6-47
IM 05P02D41-01EN
Monitoring and Control of Regular Operations
6
6.10
Changing Program Pattern during Program Operation
Description
The program pattern can be changed during the program operation in Program
Parameter Setting Display.
Unlike changing during the hold operation, changing the program pattern in Program
Parameter Setting Display saves the changed setpoint. However, even if the parameter
of the segment in process is changed, it is not reflected in operation. It is reflected from
the next operation.
In hold mode operation, it is reflected when TSP of segment is changed.
The change of the Hold-SP is reflected after release of the HOLD-mode.
► Changing Hold SP: 6.9 Changing SP, TSP, or Remaining Segment-time (R.TIM) in HOLD-mode
The program pattern cannot be changed via communication during the program
operation.