10.12SettingPresetOutputValue
10.12.3 SettingOutputValueWhenErrorOccurs(InputErrorPresetOutput)
Description
The 0% control output, 100% control output, or input preset output can be selected and
output as input error preset output in the following conditions.
• The input burnout occurs during operation in AUTO and RUN mode.
• The ADC error occurs during operation in AUTO and RUN mode.
However, the manual output becomes the output when the input burnout occurs in MAN
mode and RUN mode.
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
EPO
Input error preset
output
STD
0: Preset output
1: 0% output
2: 100% output
SYS