10.12SettingPresetOutputValue
10.12.3 SettingOutputValueWhenErrorOccurs(InputErrorPresetOutput)
Description
The 0% control output, 100% control output, or input preset output can be selected and
output as input error preset output in the following conditions.
• The input burnout occurs during operation in AUTO and RUN mode.
• The ADC error occurs during operation in AUTO and RUN mode.
However, the manual output becomes the output when the input burnout occurs in MAN
mode and RUN mode.
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
EPO
Input error preset
output
STD
0: Preset output
1: 0% output
2: 100% output
SYS