Monitoring and Control of Regular Operations
6
6.6.2 SwitchingtoPROGOperation
SelectingbyRUNKey
SettingDisplay
Press RUN key for 1 s.
PRG lamp is lit
in PROG mode.
SelectingbyOperationModeParameter
SettingDisplay
Parameter Setting Display
Operation Display > PARAMETER key or PARA key for 3
seconds (to [MODE] Menu Display) > SET/ENTER key (The
setting parameter is displayed.) > Downarrow key (The
setting parameter is displayed.)
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
MODE Operation mode EASY
RESET: Stop of program operation
PROG: Start of program operation
LOCAL: Start of local-mode
operation
MODE
Description
Program pattern operation can be performed after selecting the program pattern number
(except for 00).
Switching to PROG Operation can be performed by any of the following:
(1) RUN key (Factory default: PROG)
(2) Operation mode parameter
(3) Contact input
(4) Communication
(5) MODE key (Can be used when the user function key is not set to "PROG".)
After switching is performed by the above (2) or (5), the display is switched to SP Display.
► Switch by contact input: 12.1 Setting Contact Input Function
6.6SwitchingOperationModes