9-2
IM 05P02D41-01EN
9.1.1 SettingtheProgramPatternUsingtheSegmentTime
Description
The segment time criterion bases segment operation on the target setpoint (TSP) and
the segment time (TIME.)
The target setpoint is the control target to be attained at segment end, whereas the
segment time is the time duration from the start of that segment to the end.
PV
TIME
Time
Target setpoint of last segment
(Start target setpoint if
program just started)
Segment time
(The unit of time is
determined by “TMU”.)
Segment-n
operation
Final target setpoint:TSP
n=1 to 20 (40 when the option
“/AP” is specified.)
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
TSP
Final target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU) (Setting range: P.RL to P.RH)
PROG
TIME
Segment time
setting
EASY
-: Unregistered
0.00 to 999.59 (“hour.minute” or
“minute.second”)
If the setting is 0.00, the program advances to the next segment after one control period.
Use the parameter TMU to set the time unit. (Common in the instrument.)
When setting the program pattern via communication, set the time in minutes when the
time unit is set to hour.minute and set the time in seconds when the time unit is set to
minute.second.
9.1SettingtheSettingMethodofProgramPattern