6-49
IM 05P02D41-01EN
Monitoring and Control of Regular Operations
6
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
MAN.T
Manual output
operation type
PRO
In manual operation mode, you
can use the direct key method
or the SET/ENT key method to
control the output value. (Note)
Direct key method
Thevaluespeciedbythe
Up and Down arrow keys is
output as is.
SET/ENT key method
Set the control output on the
setting display and press the
SET/ENTkeytoconrmthe
value to output it.
OUT
Note: When the control type (CNT) is set to ON/OFF control or heating/cooling control, only the
DT.ET setting can be used. On the position proportional type, parameter MAN.T does not
appear.
6.11 Manipulating Control Output during Manual Operation