9-31
IM 05P02D41-01EN
Program Pattern Functions
9
SettingDetails
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
JC
Junction
code
STD
CONT: Switching for continuation
HOLD: Hold-on switching (the controller
holds the end-of-segment setpoint when
the segment is completed, to perform
control).
LOC: Local-mode switching (the controller
switches to a local setpoint when the
segment is completed).
W.SW1 to W.SW5: Wait during switching
between segments.
W.IV: Wait within a segment interval.
W.SL: Segment switching (the controller
switches to a local setpoint when the
segment is completed after release.)
PLK.1 to PLK.2 (PLK.4 when the option
“/AP”isspecied.):Linkedtopatterns1
to 2 (4.)
INS.: Allows a segment to be added to the
endofaspeciedsegment.
DEL.:Allowsaspeciedsegmenttobe
deleted.
PROG
9.8SettingtheOperationinSegmentSwitching