10-17
IM 05P02D41-01EN
Output (Control and Retransmission) Functions
(Continued)
Parameter
symbol
Name
Display
level
Settingrange Menusymbol
RTH
Maximum
value of
retransmission
output scale of
RET
STD
When RTS = PV1, SP1, TSP1, or PV
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When RTS=PV, decimal point position
is same as that of PV input scale.
OUT
RTL
Minimum
value of
retransmission
output scale of
RET
STD
O1RS
Retransmission
output type of
OUT current
output
STD Same as RTS
O1RH
Maximum
value of
retransmission
output scale of
OUT current
output
STD
When O1RS = PV1, SP1, TSP1, or
PV
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
When O1RS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When O1RS =PV, decimal point
position is same as that of PV input
scale.
O1RL
Minimum
value of
retransmission
output scale of
OUT current
output
STD
Setpoints HOUT1 and COUT1: Can be used in Heating/cooling control.
Setpoint MV1: Can be used in Position proportional control.
(When opening or closing a valve by key operation in manual mode opration, the transmission
output becomes -5.0 %.)
Parameters and Corresponding Terminals
RTS, RTH, RTL RET/RET2 terminal
O1RS, O1RH, O1RL OUT terminal
10
10.11SettingRetransmissionOutputTerminal,Type,andScales

Table of Contents

Other manuals for YOKOGAWA UP35A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UP35A and is the answer not in the manual?

YOKOGAWA UP35A Specifications

General IconGeneral
BrandYOKOGAWA
ModelUP35A
CategoryController
LanguageEnglish

Related product manuals