11-3
IM 05P02D41-01EN
Alarm Functions
11
DeviationHighLimitAlarmandDeviationLowLimitAlarm
PV
Alarm hysteresis
Alarm hysteresis
Deviation low limit
alarm setpoint (negative setpoint)
ON OFF
OFF
ON
OFFOFF
alarm output
Deviation low limit
alarm output
Target setpoint
(SP)
Contact type in the figure above: Energized when an event occurs (factory default).
When a negative setpoint is set for the deviation high limit alarm setpoint, the deviation setpoint will be
lower than the SP.
Moreover, when a positive setpoint is set for the deviation low limit alarm setpoint, the deviation setpoint
will be higher than the SP.
Deviation high limit
alarm setpoint (positive setpoint)
DeviationHighandLowLimitsAlarm
PV
Alarm hysteresis
Alarm hysteresis
Deviation high and
low limits alarm setpoint
ON OFF
OFF
ON
OFF
Deviation
alarm output
Target setpoint
(SP)
Contact type in the figure above: Energized when an event occurs (factory default).
DeviationwithinHighandLowLimitsAlarm
PV
Alarm hysteresis
Alarm hysteresis
Deviation within high
and low limits alarm setpoint
ON ON
OFF OFFON
Deviation within
alarm output
Target setpoint
(SP)
Contact type in the figure above: Energized when an event occurs (factory default).
11.1SettingAlarmType