EasyManua.ls Logo

Zonge GDP-32 - A Note on Phase; A Note on Scaling; A Note on Variable A-Spacing

Default Icon
419 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GDP-32
II
INSTRUCTION MANUAL
May 2002 Section 11, Page 16
11.5 A NOTE ON VARIABLE A-SPACING
When using variable A-Spacings, the key to getting the correct A-Spacing entered and used, is to
remember two things: 1) the last field changed controls the A-Spacing value that is used, and 2)
the A-Spacing that is used is ALWAYS the value in the Variable A-Spacing list.
For example, if the operator sets the A-Spacing value in the header to 50 M, then all of the
numbers in the Variable A-Spacing list are set to 50 M. If the operator then gets into the
Variable A-Spacing list and changes all of the values to, say, 25 M, then the A-Spacing value left
in the header will still be 50 M but the actual values used will be 25 M - as shown in the Variable
A-Spacing list.
The computer remembers where the latest changes were made and upon startup of the program.
The A-Spacing in the header will still be 50 M, and the values in the Variable A-Spacing cache
will still be 25 M. However, if the operator sets the A-Spacing in the header to, say, 100 M on
startup, then the Variable A-Spacing values will all be set to 100 M.
11.6 A NOTE ON PHASE
The CSAMT program is an absolute phase program - that is, the program measures the absolute
phase shift between the transmitted signal and the received signal. For normal operations at low
frequencies, the real-time phase shift should be around -100 to -200 milliradians for the E-
fields, and around +π/2 (1571 mr) for the H-fields. If the E-field phase is closer to π radians
(3142 mr) then you have some wires reversed. You can get rid of the π radians of phase shift by
either reversing the transmitter wires at the transmitter, or reversing the leads going into the
receiver. For multi-channel receivers, it is easiest to make the change at the transmitter, and then
maintain the same polarity through out the survey. If the phase for the H-field channels is
negative π/2, you have a 180 degree phase shift. The easiest way to solve this problem is to
rotate the H-field sensor by 180 degrees.
11.7 A NOTE ON SCALING
The following conventions are used for all measured and calculated parameters:
E-field Voltage, (magnitude) displayed in volts.
H-field Voltage, (magnitude) displayed in kilogammas when decalibrated with antenna cal.
Current, displayed in amperes.
Phase, displayed in milliradians.
Apparent resistivity, displayed in ohm-meters.
Dipole spacings, displayed in meters.
Coil calibrate magnitudes, entered and displayed in millivolts per gamma.
SP, displayed in millivolts
SEM, displayed in milliradians
If scaling is necessary on these values, the following labels are appended to the end of the
number string:
M - Mega units
K - Kilo units
m - milli units
u - micro units

Table of Contents

Other manuals for Zonge GDP-32

Related product manuals