17.2.2 Setting parameters
Table 611: IEC61850-8-1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
GOOSE Front
OEM311_AB
OEM311_CD
- - OEM311_AB Port for GOOSE communication
17.2.3 Technical data
Table 612: IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 608–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–19200 Bd
Protocol TCP/IP, Ethernet
Communication speed for the IEDs 100 Mbit/s
17.2.4 IEC 61850 generic communication I/O functions SPGGIO,
SP16GGIO
17.2.4.1 Introduction
IEC61850 generic communication I/O functions (SPGGIO) is used to send one single
logical signal to other systems or equipment in the substation.
17.2.4.2 Principle of operation
Upon receiving a signal at its input, IEC61850 generic communication I/O functions
(SPGGIO) function sends the signal over IEC 61850-8-1 to the equipment or system
that requests this signal. To get the signal, PCM600 must be used to define which
function block in which equipment or system should receive this information.
Section 17 1MRK505222-UUS C
Station communication
994
Technical reference manual