Name Type Default Description
IN7 BOOLEAN 0 Input 7 status
IN8 BOOLEAN 0 Input 8 status
IN9 BOOLEAN 0 Input 9 status
IN10 BOOLEAN 0 Input 10 status
IN11 BOOLEAN 0 Input 11 status
IN12 BOOLEAN 0 Input 12 status
IN13 BOOLEAN 0 Input 13 status
IN14 BOOLEAN 0 Input 14 status
IN15 BOOLEAN 0 Input 15 status
IN16 BOOLEAN 0 Input 16 status
17.2.4.5 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
17.2.5 IEC 61850 generic communication I/O functions MVGGIO
IEC61850 generic communication I/O functions (MVGGIO) function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
17.2.5.1 Principle of operation
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range, as
output values. In the same time, it will send over IEC 61850-8-1 the value, to other
IEC 61850 clients in the substation.
17.2.5.2 Function block
IEC05000408-2-en.vsd
MVGGIO
BLOCK
^IN
^VALUE
RANGE
IEC05000408 V2 EN
Figure 487: MVGGIO function block
Section 17 1MRK505222-UUS C
Station communication
996
Technical reference manual