Table 328: QCBAY Output signals
Name Type Description
PSTO INTEGER Value for the operator place allocation
UPD_BLKD BOOLEAN Update of position is blocked
CMD_BLKD BOOLEAN Function is blocked for commands
LOC BOOLEAN Local operation allowed
REM BOOLEAN Remote operation allowed
12.3.4.5 Setting parameters
Table 329: QCBAY Non group settings (basic)
Name Values (Range) Unit Step Default Description
AllPSTOValid Priority
No priority
- - Priority Priority of originators
12.3.5 Local/Remote switch LOCREM, LOCREMCTRL
12.3.5.1 Introduction
The signals from the local HMI or from an external local/remote switch are applied via
the function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)
function block. A parameter in function block LOCREM is set to choose if the switch
signals are coming from the local HMI or from an external hardware switch connected
via binary inputs.
12.3.5.2 Principle of operation
The function block Local remote (LOCREM) handles the signals coming from the local/
remote switch. The connections are seen in figure 328, where the inputs on function
block LOCREM are connected to binary inputs if an external switch is used. When the
local HMI is used, the inputs are not used and are set to FALSE in the configuration.
The outputs from the LOCREM function block control the output PSTO (Permitted
Source To Operate) on Bay control (QCBAY).
Section 12 1MRK505222-UUS C
Control
658
Technical reference manual