Logic block Quantity with cycle time Range or value Accuracy
fast medium normal
LogicGate 10 10 20 - -
LogicTimer 10 10 20 (0.000–
90000.000) s
± 0.5% ± 10 ms
LogicPulseTimer 10 10 20 (0.000–
90000.000) s
± 0.5% ± 10 ms
LogicTimerSet 10 10 20 (0.000–
90000.000) s
± 0.5% ± 10 ms
LogicLoopDelay 10 10 20 (0.000–
90000.000) s
± 0.5% ± 10 ms
Trip Matrix Logic 6 6 - - -
Boolean 16 to Integer 4 4 8 - -
Boolean 16 to
integer with Logic
Node
4 4 8 - -
Integer to Boolean 16 4 4 8 - -
Integer to Boolean
16 with Logic Node
4 4 8 - -
14.4 Fixed signal function block FXDSIGN
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fixed signals FXDSIGN - -
The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed) signals
that can be used in the configuration of an IED, either for forcing the unused inputs in
other function blocks to a certain level/value, or for creating certain logic.
14.4.1 Principle of operation
There are eight outputs from FXDSIGN function block:
OFF is a boolean signal, fixed to OFF (boolean 0) value
ON is a boolean signal, fixed to ON (boolean 1) value
INTZERO is an integer number, fixed to integer value 0
INTONE is an integer number, fixed to integer value 1
INTALONE is an integer value FFFF (hex)
REALZERO is a floating point real number, fixed to 0.0 value
1MRK505222-UUS C Section 14
Logic
881