Table 245: GOPPDOP (32) Non group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base setting for current level
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - Pos Seq Selection of measured current and voltage
7.12.6 Technical data
Table 246: GOPPDOP (32) technical data
Function Range or value Accuracy
Power level (0.0–500.0)% of S
base
At low setting:
(0.5-2.0)% of S
base
(2.0-10)% of S
base
± 1.0% of S
r
at S < S
r
± 1.0% of S at S > S
r
< ± 50% of set value
< ± 20% of set value
Characteristic angle (-180.0–180.0) degrees 2 degrees
Timers (0.00-6000.00) s ± 0.5% ± 10 ms
7.13 Broken conductor check BRCPTOC (46)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Broken conductor check BRCPTOC - 46
7.13.1 Introduction
Conventional protection functions can not detect the broken conductor condition.
Broken conductor check (BRCPTOC, 46) function, consisting of continuous current
unsymmetrical check on the line where the IED is connected will give alarm or trip at
detecting broken conductors.
Section 7 1MRK505222-UUS C
Current protection
486
Technical reference manual