12.6.4 Input and output signals
Table 384: VSGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input
Table 385: VSGGIO Output signals
Name Type Description
BLOCKED BOOLEAN The function is active but the functionality is blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1
12.6.5 Setting parameters
Table 386: VSGGIO Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
CtlModel Dir Norm
SBO Enh
- - Dir Norm Specifies the type for control model according
to IEC 61850
Mode Steady
Pulsed
- - Pulsed Operation mode
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght
12.7 IEC61850 generic communication I/O functions
DPGGIO
Section 12 1MRK505222-UUS C
Control
762
Technical reference manual