EasyManua.ls Logo

ABB Relion 670 series - Input and output signals; Setting parameters; IEC61850 generic communication I;O functions DPGGIO

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.6.4 Input and output signals
Table 384: VSGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input
Table 385: VSGGIO Output signals
Name Type Description
BLOCKED BOOLEAN The function is active but the functionality is blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1
12.6.5 Setting parameters
Table 386: VSGGIO Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
CtlModel Dir Norm
SBO Enh
- - Dir Norm Specifies the type for control model according
to IEC 61850
Mode Steady
Pulsed
- - Pulsed Operation mode
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght
12.7 IEC61850 generic communication I/O functions
DPGGIO
Section 12 1MRK505222-UUS C
Control
762
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series