17.6.5  Setting parameters
Table 651: IEC60870-5-103 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 0 - 255 - 1 30 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
RevPolarity Disabled
Enabled
- - Enabled Invert polarity
CycMeasRepTime 1.0 - 3600.0 - 0.1 5.0 Cyclic reporting time of measurments
Table 652: I103IEDCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 255 Function type (1-255)
Table 653: I103CMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
Table 654: I103USRCMD Non group settings (basic)
Name
Values (Range) Unit Step Default Description
PULSEMOD 0 - 1 Mode 1 1 Pulse mode 0=Steady, 1=Pulsed
T 0.200 - 60.000 s 0.001 0.400 Pulse length
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
INFNO_1 1 - 255 InfNo 1 1 Information number for output 1 (1-255)
INFNO_2 1 - 255 InfNo 1 2 Information number for output 2 (1-255)
INFNO_3 1 - 255 InfNo 1 3 Information number for output 3 (1-255)
INFNO_4 1 - 255 InfNo 1 4 Information number for output 4 (1-255)
INFNO_5 1 - 255 InfNo 1 5 Information number for output 5 (1-255)
INFNO_6 1 - 255 InfNo 1 6 Information number for output 6 (1-255)
INFNO_7 1 - 255 InfNo 1 7 Information number for output 7 (1-255)
INFNO_8 1 - 255 InfNo 1 8 Information number for output 8 (1-255)
Table 655: I103IED Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)
1MRK505222-UUS C Section 17
Station communication
1055