EasyManua.ls Logo

ABB Relion 670 series - Function block; Input and output signals

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.13.3 Function block
ANSI10000045-1-en.vsd
PSPPPAM (78)
I3P*
V3P*
BLOCK
BLKGEN
BLKMOTOR
EXTZONE1
TRIP
TRIP1
TRIP2
PICKUP
ZONE1
ZONE2
GEN
MOTOR
SFREQ
SLIPZOHM
SLIPZPER
VCOS
VCOSPER
ANSI10000045 V1 EN
Figure 195: PSPPPAM (78) function block
6.13.4 Input and output signals
Table 169: PSPPPAM (78) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Current group connection
V3P GROUP
SIGNAL
- Voltage group connection
BLOCK BOOLEAN 0 Block of function
BLKGEN BOOLEAN 0 Block operation in generating direction
BLKMOTOR BOOLEAN 0 Block operation in motor direction
EXTZONE1 BOOLEAN 0 Extension of zone1 with zone2 region
Table 170: PSPPPAM (78) Output signals
Name
Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip1 after the N1Limit slip in zone1
TRIP2 BOOLEAN Trip2 after the N2Limit slip in zone2
PICKUP BOOLEAN Common start signal
ZONE1 BOOLEAN First slip in zone1 region
ZONE2 BOOLEAN First slip in zone2 region
GEN BOOLEAN Generator is faster than the system
MOTOR BOOLEAN Generator is slower than the system
SFREQ REAL Slip frequency
Table continues on next page
Section 6 1MRK505222-UUS C
Impedance protection
366
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals