IEC05000716_2_en.vsd
SETGRPS
MAXSETGR
IEC05000716 V2 EN
Figure 31: SETGRPS function block
4.4.4 Input and output signals
Table 29: ActiveGroup Input signals
Name Type Default Description
ACTGRP1 BOOLEAN 0 Selects setting group 1 as active
ACTGRP2 BOOLEAN 0 Selects setting group 2 as active
ACTGRP3 BOOLEAN 0 Selects setting group 3 as active
ACTGRP4 BOOLEAN 0 Selects setting group 4 as active
ACTGRP5 BOOLEAN 0 Selects setting group 5 as active
ACTGRP6 BOOLEAN 0 Selects setting group 6 as active
Table 30: ActiveGroup Output signals
Name
Type Description
GRP1 BOOLEAN Setting group 1 is active
GRP2 BOOLEAN Setting group 2 is active
GRP3 BOOLEAN Setting group 3 is active
GRP4 BOOLEAN Setting group 4 is active
GRP5 BOOLEAN Setting group 5 is active
GRP6 BOOLEAN Setting group 6 is active
GRP_CHGD BOOLEAN Pulse when setting changed
4.4.5 Setting parameters
Table 31: ActiveGroup Non group settings (basic)
Name
Values (Range) Unit Step Default Description
t 0.0 - 10.0 s 0.1 1.0 Pulse length of pulse when setting changed
1MRK505222-UUS C Section 4
Basic IED functions
97
Technical reference manual