EasyManua.ls Logo

ABB Relion 670 series - Technical data

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
IMinPUPG 5 - 30 %IB 1 5 Minimum pickup phase current for Phase-to-
ground loops
AngNegRes 90 - 175 Deg 1 115 Angle of blinder in second quadrant for
forward direction
AngDir 5 - 45 Deg 1 15 Angle of blinder in fourth quadrant for forward
direction
6.9.6 Technical data
Table 155: ZMRPDIS, ZMRAPDIS (21) technical data
Function Range or value Accuracy
Number of zones Max 5 with selectable
direction
-
Minimum operate residual
current, zone 1
(5-1000)% of IBase -
Minimum operate current, phase-
to-phase and phase-to-ground
(10-1000)% of IBase -
Positive sequence reactance (0.10-3000.00) Ω/
phase
± 2.0% static accuracy
± 2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Angle: at 0 degrees and 85 degrees
Positive sequence resistance (0.01-1000.00) Ω/
phase
Zero sequence reactance (0.10-9000.00) Ω/
phase
Zero sequence resistance (0.01-3000.00) Ω/
phase
Fault resistance, phase-to-
ground
(0.10-9000.00) Ω/loop
Fault resistance, phase-to-phase (0.10-3000.00) Ω/loop
Dynamic overreach <5% at 85 degrees
measured with CVT’s
and 0.5<SIR<30
-
Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms
Operate time 24 ms typically -
Reset ratio 105% typically -
Reset time 30 ms typically -
1MRK505222-UUS C Section 6
Impedance protection
325
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals