Table 521: RSMEMORY Output signals
Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
Table 522: RSMEMORY Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Disabled
Enabled
- - Enabled Operating mode of the memory function
14.3.11 Controllable gate function block GATE
The Controllable gate function block (GATE) is used for controlling if a signal should
be able to pass from the input to the output or not depending on a setting.
IEC04000410-2-en.vsd
GATE
INPUT OUT
IEC04000410 V2 EN
Figure 445: GATE function block
Table 523: GATE Input signals
Name
Type Default Description
INPUT BOOLEAN 0 Input to gate
Table 524: GATE Output signals
Name
Type Description
OUT BOOLEAN Output from gate
Table 525: GATE Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
1MRK505222-UUS C Section 14
Logic
879
Technical reference manual