14.1.5 Setting parameters
Table 493: SMPPTRC (94) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
Program 3 phase
1p/3p
1p/2p/3p
- - 1p/3p Three pole; single or three pole; single, two or
three pole trip
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secures 3-pole trip when phase selection
failed
Table 494: SMPPTRC (94) Group settings (advanced)
Name Values (Range) Unit Step Default Description
TripLockout Disabled
Enabled
- - Disabled If TripLockout is set to On, it will activate
output (CLLKOUT) and trip latch. If set to Off
it will activate only CLLKOUT
AutoLock Disabled
Enabled
- - Disabled If AutoLock is set to On i will activate lockout
from input (SETLKOUT) and trip, If set to Off
it will activate only from SETLKOUT
14.1.6 Technical data
Table 495: SMPPTRC (94) technical data
Function
Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms
Timers (0.000-60.000) s ± 0.5% ± 10 ms
14.2 Trip matrix logic TMAGGIO
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic TMAGGIO - -
1MRK505222-UUS C Section 14
Logic
867
Technical reference manual