EasyManua.ls Logo

ABB Relion 670 series - Sensitive directional residual overcurrent and power protection SDEPSDE (67 N); Introduction

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.6 Sensitive directional residual overcurrent and power
protection SDEPSDE (67N)
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sensitive directional residual over
current and power protection
SDEPSDE - 67N
7.6.1 Introduction
In networks with high impedance grounding, the phase-to-ground fault current is
significantly smaller than the short circuit currents. Another difficulty for ground-fault
protection is that the magnitude of the phase-to-ground fault current is almost
independent of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-to-
ground faults in high impedance grounded networks. The protection uses the residual
current component 3I
0
· cos φ, where φ is the angle between the residual current and
the residual voltage (-3V
0
), compensated with a characteristic angle. Alternatively, the
function can be set to strict 3I
0
level with a check of angle 3I
0
and cos φ.
Directional residual power can also be used to detect and give selective trip of phase-to-
ground faults in high impedance grounded networks. The protection uses the residual
power component 3I
0
· 3V
0
· cos φ, where φ is the angle between the residual current
and the reference residual voltage, compensated with a characteristic angle.
A normal non-directional residual current function can also be used with definite or
inverse time delay.
A back-up neutral point voltage function is also available for non-directional sensitive
back-up protection.
In an isolated network, that is, the network is only coupled to ground via the
capacitances between the phase conductors and ground, the residual current always has
-90º phase shift compared to the reference residual voltage. The characteristic angle is
chosen to -90º in such a network.
In resistance grounded networks or in Petersen coil grounded, with a parallel resistor,
the active residual current component (in phase with the residual voltage) should be
used for the ground-fault detection. In such networks the characteristic angle is chosen
to 0º.
Section 7 1MRK505222-UUS C
Current protection
436
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals