16.1.5  Setting parameters
Table 605: PCGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable/Disable
EventMask NoEvents
ReportEvents
- - NoEvents Report mask for analog events from pulse
counter
CountCriteria Disabled
RisingEdge
Falling edge
OnChange
- - RisingEdge Pulse counter criteria
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to unit
per counted value
Quantity Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
- - Count Measured quantity for SCAL_VAL output
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value
16.1.6  Technical data
Table 606: PCGGIO technical data
Function
Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of
counter value
(1–3600) s -
16.2  Function for energy calculation and demand handling
ETPMMTR
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Energy calculation and demand
handling
ETPMMTR   -
1MRK505222-UUS C Section 16
Metering
987
Technical reference manual