Table 350: RESIN2 Output signals
Name Type Description
ACK_F_B BOOLEAN All other bays have acknowledged the reservation
request from this bay
ANY_ACK BOOLEAN Any other bay has acknowledged the reservation
request from this bay
VALID_TX BOOLEAN The reservation and acknowledge signals from other
bays are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn
blocks
12.3.10.5 Setting parameters
Table 351: RESIN1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
FutureUse Bay in use
Bay future use
- - Bay in use The bay for this ResIn block is for future use
Table 352: RESIN2 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FutureUse Bay in use
Bay future use
- - Bay in use The bay for this ResIn block is for future use
12.4 Interlocking (3)
12.4.1 Introduction
The interlocking functionality blocks the possibility to operate high-voltage switching
devices, for instance when a disconnector is under load, in order to prevent material
damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The interlocking functionality in each IED is
not dependent on any central function. For the station-wide interlocking, the IEDs
communicate via the station bus or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the
system at any given time.
Section 12 1MRK505222-UUS C
Control
690
Technical reference manual