The software needed in the PC, either local or remote, is PCM600.
When communicating between the local HMI and a PC, the only hardware required is
a front-connection cable.
17.5.4  Setting parameters
Table 633: SPA Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 899 - 1 30 Slave address
BaudRate 300 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
- - 9600 Bd Baudrate on serial line
Table 634: LONSPA Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation
SlaveAddress 1 - 899 - 1 30 Slave address
17.5.5  Technical data
Table 635: SPA communication protocol
Function
Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
17.6  IEC 60870-5-103 communication protocol
17.6.1  Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.
Section 17 1MRK505222-UUS C
Station communication
1036
Technical reference manual