EasyManua.ls Logo

ABB Relion 670 series - Additional distance protection directional function for ground faults ZDARDIR

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
reactance phase C
direction phase A
direction phase B
direction phase C
6.6.2.2 Additional distance protection directional function for ground faults
ZDARDIR
A Mho element needs a polarizing voltage for its operation. The positive-sequence
memory-polarized elements are generally preferred. The benefits include:
The greatest amount of expansion for improved resistive coverage. These elements
always expand back to the source.
Memory action for all fault types. This is very important for close-in three-phase
faults.
A common polarizing reference for all six distance-measuring loops. This is
important for single-pole tripping, during a pole-open period.
There are however some situations that can cause security problems like reverse phase
to phase faults and double phase-to-ground faults during high load periods. To solve
these, additional directional element is used.
For phase-to-ground faults, directional elements using sequence components are very
reliable for directional discrimination. The directional element can be based on one of
following types of polarization:
Zero-sequence voltage
Negative-sequence voltage
Zero-sequence current
These additional directional criteria are evaluated in the Additional distance protection
directional function for ground faults (ZDARDIR).
Zero-sequence voltage polarization is utilizing the phase relation between the zero-
sequence voltage and the zero-sequence current at the location of the protection. The
measurement principle is illustrated in figure
143.
Section 6 1MRK505222-UUS C
Impedance protection
280
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals