Figure 131: The different measuring loops at line-ground fault and phase-phase fault.
6.5.2.2  Impedance characteristic
The distance measuring zone include three impedance measuring loops; one fault loop
for each phase.
The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in figure 
132. The characteristic is illustrated with
the full loop reach.