Figure 131: The different measuring loops at line-ground fault and phase-phase fault.
6.5.2.2 Impedance characteristic
The distance measuring zone include three impedance measuring loops; one fault loop
for each phase.
The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in figure
132. The characteristic is illustrated with
the full loop reach.
1MRK505222-UUS C Section 6
Impedance protection
263
Technical reference manual