There is an operation mode (OpModeSel) setting: 1 out of 3 or 2 out of 3. If the
parameter is set to 1 out of 3 any phase trip signal will be activated. If the parameter is
set to 2 out of 3 at least two phase signals must be activated for trip.
There is also a possibility to activate a preset change of the set operation current
(MultPU) via a binary input (MULTPU). In some applications the operation value
needs to be changed, for example due to transformer inrush currents.
PHPIOC (50) can be blocked from the binary input BLOCK.
7.1.3 Function block
ANSI04000391-2-en.vsd
PHPIOC (50)
I3P*
BLOCK
MULTPU
TRIP
TR_A
TR_B
TR_C
ANSI04000391 V2 EN
Figure 200: PHPIOC (50) function block
7.1.4 Input and output signals
Table 184: PHPIOC (50) Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- Three phase current
BLOCK BOOLEAN 0 Block of function
MULTPU BOOLEAN 0 Enable current pickup value multiplier
Table 185: PHPIOC (50) Output signals
Name
Type Description
TRIP BOOLEAN Trip signal from any phase
TR_A BOOLEAN Trip signal from phase A
TR_B BOOLEAN Trip signal from phase B
TR_C BOOLEAN Trip signal from phase C
Section 7 1MRK505222-UUS C
Current protection
380
Technical reference manual