12.3.10.4 Input and output signals
Table 347: RESIN1 Input signals
Name Type Default Description
BAY_ACK BOOLEAN 0 Another bay has acknowledged the reservation
request from this bay
BAY_VAL BOOLEAN 0 The reservervation and acknowledge signals from
another bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay
Table 348: RESIN1 Output signals
Name Type Description
ACK_F_B BOOLEAN All other bays have acknowledged the reservation
request from this bay
ANY_ACK BOOLEAN Any other bay has acknowledged the reservation
request from this bay
VALID_TX BOOLEAN The reservation and acknowledge signals from other
bays are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn
blocks
Table 349: RESIN2 Input signals
Name
Type Default Description
EXCH_IN INTEGER 5 Used for exchange signals between different ResIn
blocks
BAY_ACK BOOLEAN 0 Another bay has acknowledged the reservation
request from this bay
BAY_VAL BOOLEAN 0 The reservervation and acknowledge signals from
another bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay
1MRK505222-UUS C Section 12
Control
689
Technical reference manual