4.2 Self supervision with internal event list
4.2.1 Introduction
Self supervision with internal event list function listens and reacts to internal system
events, generated by the different built-in self-supervision elements. The internal
events are saved in an internal event list.
4.2.2 Principle of operation
The self-supervision operates continuously and includes:
Normal micro-processor watchdog function.
Checking of digitized measuring signals.
Other alarms, for example hardware and time synchronization.
The self-supervision function status can be monitored from the local HMI, from the
Event Viewer in PCM600 or from a SMS/SCS system.
Under the Diagnostics menu in the local HMI the present information from the self-
supervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/General.
The information from the self-supervision function is also available in the Event
Viewer in PCM600.
A self-supervision summary can be obtained by means of the potential free alarm
contact (INTERNAL FAIL) located on the power supply module. The function of this
output relay is an OR-function between the INT-FAIL signal see figure
22 and a
couple of more severe faults that can occur in the IED, see figure 21
Section 4 1MRK505222-UUS C
Basic IED functions
78
Technical reference manual