Name Values (Range) Unit Step Default Description
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for programmable over voltage
TOV curve, step 2
8.3.6 Technical data
Table 268: ROV2PTOV (59N) technical data
Function Range or value Accuracy
Operate voltage, step 1
and step 2
(1-200)% of
VBase
± 0.5% of V
n
at V < V
n
± 1.0% of V at V > V
n
Absolute hysteresis (0–100)% of
VBase
± 0.5% of V
n
at V < V
n
± 1.0% of V at V > V
n
Inverse time
characteristics for low
and high step, see
table
733
- See table 733
Definite time setting, step
1
(0.00–6000.00) s ± 0.5% ± 10 ms
Definite time setting (0.000–60.000) s ± 0.5% ± 10 ms
Minimum operate time (0.000-60.000) s ± 0.5% ± 10 ms
Operate time, pickup
function
25 ms typically at 0 to 2 x V
set
-
Reset time, pickup
function
25 ms typically at 2 to 0 x V
set
-
Critical impulse time 10 ms typically at 0 to 2 x V
set
-
Impulse margin time 15 ms typically -
Section 8 1MRK505222-UUS C
Voltage protection
528
Technical reference manual