Name Values (Range) Unit Step Default Description
TD1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay for
step 1
HystAbs1 0.0 - 100.0 %VB 0.1 0.5 Absolute hysteresis in % of VBase, step 1
OperationStep2 Disabled
Enabled
- - Enabled Enable execution of step 2
Characterist2 Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
- - Definite time Selection of time delay curve type for step 2
Pickup2 1 - 100 %VB 1 45 Voltage setting/pickup value (DT & TOV),
step 2 in % of VBase
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves for
step 2
TD2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay for
step 2
HystAbs2 0.0 - 100.0 %VB 0.1 0.5 Absolute hysteresis in % of VBase, step 2
Table 267: ROV2PTOV (59N) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1 Instantaneous
Frozen timer
Linearly decreased
- - Instantaneous Selection of used IDMT reset curve type for
step 1
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for programmable over voltage
TOV curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Time delay in Definite-Time reset (s), step 2
ResetTypeCrv2 Instantaneous
Frozen timer
Linearly decreased
- - Instantaneous Selection of Time Delay reset curve for step 2
Table continues on next page
1MRK505222-UUS C Section 8
Voltage protection
527
Technical reference manual