EasyManua.ls Logo

ABB Relion 670 series - Minimum operating current; Measuring principles

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en05000182.vsd
R
X
R
X
R
X
Non-directional Forward Reverse
IEC05000182 V1 EN
Figure 161: Directional operating modes of the distance measuring zones
6.9.2.3 Minimum operating current
The operation of Distance measuring zones, quadrilateral characteristic (ZMRPDIS,
21) is blocked if the magnitude of input currents fall below certain threshold values.
The phase-to-ground loop AG (BG or CG) is blocked if IA (IB or IC) < IMinPUPG.
For zone 1 with load compensation feature the additional criterion applies, that all phase-
to-ground loops can be blocked when IN < IMinOpIR, regardless of the phase currents.
IA (IB or IC) is the RMS value of the current in phase IA (IB or IC). IN is the RMS
value of the vector sum of the three-phase currents, that is residual current 3I
0
.
The phase-to-phase loop AB (BC or CA) is blocked if I
AB (BC or CA)
< IMinPUPP.
All three current limits IMinPUPG, IMinOpIR and IMinPUPP are
automatically reduced to 75% of regular set values if the zone is set to
operate in reverse direction, that is OperationDir=Reverse
6.9.2.4 Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The
Section 6 1MRK505222-UUS C
Impedance protection
310
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals