15.1.5 Setting parameters
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM600.
Table 552: CVMMXN Non group settings (basic)
Name Values (Range) Unit Step Default Description
SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
PRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VMin 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of UBase
VMax 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of UBase
VRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IMin 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
Table continues on next page
1MRK505222-UUS C Section 15
Monitoring
913